Skip to content
  • QUOTE
  • 888.653.333
  • info@safti.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
  • Literature
  • Specs
  • Details
  • Learn
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Gallery
  • Reps
  • Contact
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Articles
Code Education
FAQ Fire Rated Glass in Sidelites and Transoms
Code Education

FAQ Fire Rated Glass in Sidelites and Transoms

ByDiana S
| November 26, 2014

FAQ Fire Rated Glass in Sidelites and Transoms

FAQ Fire Rated Glass in Sidelites and Transoms. What do the codes say about the application of fire rated glass and framing in sidelites and transoms?

Why do codes sometimes require sidelites & transoms to have higher ratings than doors?

When the code requires fire doors rated 1-hour or more, then the sidelites and transoms around that door must be fire resistive and rated to the same standard as the wall itself (e.g., 1-or 2-hour). Sidelites and transoms around a 20-minute fire door in a 1-hour exit require a 45-minute fire rating with hose stream.

Why does the rating have to equal that of the wall, and not the door opening?

Unlike a door, which is actively opened and closed, and has a limited surface area, fixed panels present a greater radiant heat risk. Combustibles cannot be stored against an operable door, but can be stored against a fixed sidelite. Additionally, a door opening has a limited surface area, whereas a fixed sidelite and transom is limited only by the size in which it can pass the fire test. Because of the concern about fire spread due to combustibles igniting from high levels of radiant heat, safe fire protection engineering principles dictate the limited use of fire protective materials in 60- and 90-minute doors to the door vision panel, and require glazing around the door to meet the requirements of the wall itself.

Does that mean sidelites and transoms cannot be used around 60- and 90-minute doors?

No, but the fire rated glazing used must be a fire resistive rated material (NOT wired glass or ceramic, which are fire protective materials). In addition, the rating of the sidelite and transom must equal that of the wall, not of the door opening.

In a sprinklered building, can you increase the size of the door vision panel in an exit/stairwell enclosure?

No. In the 2000 IBC, an exception was provided that allowed the use of non-temperature rise doors if a building was fully sprinklered in accordance with Chapter 9. The 2012 IBC was amended to clarify that the maximum allowable vision panel in a 60-or 90-minute, temperature rise door in an exit enclosure or passageway is 100 sq inches, regardless of whether the building is fully sprinklered or not. The only way to increase the size of a vision panel in a 60-or 90-minute door in an exit/stairwell enclosure is to use fire resistive glazing.

What is the difference between a fire protective and fire resistive glazing product?

Fire resistive glass has the ability to significantly limit radiant heat transfer, having been tested to ASTM E-119, the more stringent fire test requirements of a wall. Fire protective glazing cannot limit radiant heat or meet ASTM E-119. Indeed, many fire protective materials allow dangerous levels of radiant heat flux to pass right through the glazing in the first few minutes of a fire. In general, fire protective products can be used for 20-45 minute applications and fire resistive products can be used in applications over 45 minutes.

Code Compliant Example

90-minute doors and 2-hour wall in a 2-hour exit passageway at Freedom High School, Bethlehem, Pennsylvania.

Products used: SuperLite II-XL 90 (doors) and SuperLite II-XL 120 (walls) in GPX framing. Both glazing products are fire resistive, block radiant heat, rated 90- (doors) and 120- (sidelites, transoms) minutes with hose stream, impact safety rated to CPSC Cat II, and meet ASTM E-119.

FAQ Fire Rated Glass in Sidelites and Transoms

Got questions on fire rated glass and framing? Train with a recognized code expert while earning 1 AIA LU and 1 HSW credit with our AIA-accredited webinar program “Designing with Fire Rated Glass”.

To schedule a free webinar for your firm, send an email to dianas@safti.com. For more information on SAFTI FIRST’s products, please visit www.stage.safti.com.

Share:
PrevNext ArticleFAQ Fire Rated Framing Code Requirements
Previous ArticleFAQ Fire Rated Glass in Stairwell EnclosuresNext
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • info@safti.com
  • Representative Map
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
info@safti.com

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

© 2023 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Twitter Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Videos Archive [INACTIVE]
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}