Skip to content
  • QUOTE
  • 888.653.333
  • info@safti.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
  • Literature
  • Specs
  • Details
  • Learn
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Gallery
  • Reps
  • Contact
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Articles
Code Education
Fire Protective vs Fire Resistive Glazing
Code Education

Fire Protective vs Fire Resistive Glazing

ByDiana S
| November 26, 2014

The differences between Fire Protective and Fire Resistive Glazing.

Fire Protective vs Fire Resistive Glazing? It is important to know the difference in determining whether an installation complies with codes. Each category has its own set of performance features, test standards and allowed applications. Simply relying on the fire endurance rating (20, 45, 60, 90, 120 and 180 minutes) or whether a product is “thick” or “thin” can lead to faulty specifications and misapplications of the product.  This article discusses the difference between fire protective and fire resistive glazing based on NFPA, UL & ASTM test standards and IBC code requirements.

Fire protective glass is designed to compartmentalize smoke and flames and is subject to application, area and size limitations under the IBC. Fire protective glass is typically used in doors and openings up to 45 minutes and cannot exceed 25% of the total wall area because it does not block radiant heat transmission. These products are also subject to the following test standards:

  • NFPA 252, Standard Methods of Fire Tests of Door Assemblies
  • NFPA 257, Standard on Fire Tests for Window and Glass Block Assemblies
  • UL 9, Standard for Safety Fire Tests of Window Assemblies
  • UL 10B, Fire Tests of Door Assemblies
  • UL 10C, Positive Pressure Fire Tests of Door Assemblies

Fire protective glass products include:

Type Fire Rating CPSC Safety Rating Appearance Typical Application(s)
Specialty Tempered 20 minutes CPSC Cat. II Optically clear. No wires or tints. Doors up to the max. size tested
Specialty Tempered, Heat Reflective 20-60 minutes
AHJ approval is required for 45-60 minute applications.
CPSC Cat. II Optically clear. No wires or tints. 20-45 min. doors up to the max. size tested / 60 min. doors up to 100 sq. in. / 45 min. sidelites, transoms and windows
Specialty Fire Protective 90 minutes CPSC Cat. I or Cat. II Optically clear. No wires or tints. 90 min. doors up to 100 sq. in.
Traditional Wired Glass 20-90 minutes none Annealed glass with embedded wires. 45 min. transoms and windows where safety is not a requirement
Safety Wired Glass 20-90 minutes CPSC Cat. II Wired glass with surface applied safety film 20-45 min. doors up to the max. size tested / 60-90 min. doors up to 100 sq. in. / 45 min. sidelites, transoms and windows
Ceramic 20-90 minutes none Wire-free with amber tints 45 min. transoms and windows where safety is not a requirement
Filmed Safety Ceramic 20-180 minutes CPSC Cat. II Ceramic with surface applied safety film. Wire-free with amber tints. 20-45 min. doors up to the max. size tested / 60-180 min. doors up to 100 sq. in. / 45 min. sidelites, transoms and windows
Laminated Safety Ceramic 20-180 minutes CPSC Cat. II Laminated ceramic. Wire-free with amber tints. 20-45 min. doors up to the max. size tested / 60-180 min. doors up to100 sq. in. / 45 min. sidelites, transoms and windows

It is important to note that while there are fire protective products rated from 60 to 180 minutes, their application is limited to door vision panels, and size limitations may apply. For 180 minute doors, fire protective products may be listed for 100 square inches, although the IBC does not permit any vision panel in a 3-hour rated fire door. For 60 and 90 minute doors in exit enclosures and exit passageways, fire protective products are limited to 100 square inches whether or not the building is fully sprinklered. More information on the code change and the 2012 IBC are discussed in following sections.

In addition, fire protective glass, such as ceramics and wired glass, have limited use in 1-hour walls, and are prohibited altogether as sidelites, transoms and windows in 2-hour interior walls because they cannot block radiant heat. These limitations are recognized in the IBC, and recent revisions to the 2012 IBC give end-users clear guidance in applying those limits.

Fire resistive glass is not limited in application or size. This type of FRG compartmentalizes smoke and flames, and blocks the transmission of dangerous levels of radiant heat through the glazing. As a result, it can be used in wall and door applications 60 minutes and above without the size limitations that apply to fire protective glass. The following test standards apply to fire resistive glass:

  • ASTM E-119, Standard Methods for Fire Tests of Building Construction and Materials
  • NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials
  • UL 263, Fire Tests of Building Construction and Materials

These standards apply to all fire-resistive wall materials, where the temperature rise on the non-fire side cannot exceed an average of 250 degrees Fahrenheit. The intent is to block the dangerous transmission of radiant heat, which can cause paper, drapes, clothing and other combustible materials within 20 feet to ignite without coming in contact with the actual fire. Imagine the devastating effect unrestricted radiant heat has on building occupants attempting to exit past a large glazed area during a fire. By effectively compartmentalizing smoke, flames and radiant heat, fire resistive glass insures safe egress, no matter how large the glazed area.

Fire resistive glass products include:

Type Fire Rating CPSC Safety Rating Appearance Typical Application(s)
Fire retardant filled units Up to 2 hours CPSC Cat. II Optically clear. No wires or tints. Comprised of 2 tempered lites with the cavity filled with a clear fire retardant. 1-2 hour walls, 60-90 min. doors and 60-120 min. sidelites and transoms up to the max. size tested
Multilaminates Up to 2 hours CPSC Cat. II Optically clear. No wires or tints. Multiple sheets of annealed glass with an intumescent interlayer. 1-2 hour walls, 60-90 min. doors and 60-120 min. sidelites and transoms up to the max. size tested
Fire Protective vs Fire Resistive Glazing
Fire Protective vs. Fire Resistive Glass

Framing Must Match Glazing Requirements

Because fire rated glass is used in door and wall assemblies, code requirements for framing must also be considered. Simply put, the fire rated framing requirements must match the glazing requirements in order for the assembly to fully meet the requirements of the code.

Fire protective framing, like fire protective glazing, has limited use in applications rated over 45 minutes. The most common frame is hollow metal. This type of framing can be used in doors, sidelites, transoms and interior windows up to 45 minutes. Fire protective, hollow metal frames, like fire protective glazing, fail to block the spread of radiant heat.

Fire Protective vs Fire Resistive Glazing
Hollow Metal Hot Rolled Steel Section

Fire resistive framing has the ability to block the spread of radiant heat. Like fire resistive glazing, this type of framing meets ASTM E-119/NFPA 251/UL 263 requirements. Fire resistive framing can be used in wall and door assemblies (this includes glazing around and over the door, such as sidelites and transoms) rated 60 minutes and above.

Project specifications that configure fire resistive glazing in hollow metal frames in 1 or 2 hour applications fail to meet code, because fire resistive glazing with fire protective framing lowers the overall fire performance rating of the assembly to fire protective. In 1 or 2 hour applications where meeting ASTM E-119/NFPA 251/UL 263 is required, both the glazing and framing must be fire resistive.

Fire Protective vs Fire Resistive Glazing
Fire Resistive Framing with Fire Resistive Glazing
Share:
PrevNext ArticleFire Rated Glass Code FAQs
Previous ArticleTop Five Fire Rated Glass Code MistakesNext
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • info@safti.com
  • Representative Map
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
info@safti.com

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

© 2023 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Twitter Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Videos Archive [INACTIVE]
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}