Skip to content
  • QUOTE
  • 888.653.3333
  • info@stage.safti.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
    • Specialty Glass
    • Laminated Safety Glass
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Gallery
  • Contact
    Contact Us
    Meet Our Team
    Find Your Local Rep
    Request a Quote
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Contact
    • Contact Us
    • Meet Our Team
    • Find Your Local Rep
    • Request a Quote
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Contact
    • Contact Us
    • Meet Our Team
    • Find Your Local Rep
    • Request a Quote
Articles
Code Education
Learn more about the Testing Standards for Fire Rated Glass Applications
Code Education

Learn more about the Testing Standards for Fire Rated Glass Applications

BySAFTI FIRST Team
| June 5, 2018

Testing Standards for Fire Rated Glass Applications

When it comes to fire rated glass and framing, how a system is tested is important in determining its approved applications in the International Building Code (IBC). In fact, many of the test standards such as NFPA 252, NFPA 257, ASTM E-119, UL 263, etc. are directly referenced in the Chapter 7 tables of the IBC, where fire rated glass applications can be found.

Click here to download the 2012 IBC Chapter 7 Tables
Click here to download the 2015 IBC Chapter 7 Tables

Click here to download the 2018 IBC Chapter 7 Tables

These tests must be conducted by a nationally recognized testing laboratory (NRTL) and the product must remain in its follow-up service. When the fire rated glass product or system passes, it is given a listing and label from the test lab. Note that the listing and label provided by the test lab only show what the product or system has been tested to it does not equal code compliance. This a common misunderstanding in our industry, and one that has led to many misapplications that cause potential delays and added costs to the project.

In order to avoid these costly mistakes, it is important to understand the required test procedures referenced in the IBC as it relates to the fire rated glass product’s application: whether it is used in windows, doors, walls or floors.

Fire Window Assembly Testing Standards

Fire window assemblies are tested to NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies or UL 9, Standard for Fire Tests of Window Assemblies. The glazing product is subject to the fire endurance test and hose stream test. Since measuring radiant heat transmission is not part of the test, these products are classified as fire protective and are subject to application and size limitations. Interior windows or openings are limited to 20-45 minutes and 25% of the wall area. Exterior windows or openings are permitted up to 90 minutes, but their applications and sizes are limited in the IBC based on the fire separation distance.

Fire Rated Glass Testing for Windows, Doors, Walls and Floors
Interior fire windows or openings are rated up to 45 minutes and limited to 25% of the wall area in 1 hour fire partitions/corridors, smoke barriers, incidental use areas and mixed occupancy separations per Table 716.6 in the 2012/2015 IBC and Table 716.1(3) in the 2018 IBC

Fire Door Assembly Testing Standards

Fire door assemblies (includes the door panel, sidelite and transoms) are tested to NFPA 252, Standard Methods of Fire Tests of Door Assemblies or UL 10 B, Standard for Fire Tests of Door Assemblies, or UL 10 C, Standard for Positive Pressure Fire Tests of Door Assemblies. In the late 1990s, the required test method changed from neutral or negative pressure to positive pressure to more accurately simulate the conditions of a fire in the real world. Today, the IBC requires side-hinged or swinging fire doors to be tested with positive pressure, using either UL 10C or NFPA 252. Like fire window assemblies, fire door assembly testing includes the fire endurance test and hose stream test. Note that building codes throughout the US typically stipulate that 20 minute doors are exempt from the hose stream test.

Fire Rated Glass Testing for Windows, Doors, Walls and Floors
20-45 minute door assemblies do not need to meet temperature rise door requirements. They are typically found in 1 hour fire partitions/corridors and smoke barriers per Table 716.5 in the 2012/2015 IBC and Table 716.1(2) in the 2018 IBC.

In certain applications, fire doors are also required to limit the transmission of heat from one side to the other to protect building occupants so they can safely exit the building. Known as temperature rise doors, these doors carry a temperature rise rating in addition to the hourly rating. Temperature rise ratings are either 250 degrees F, 450 degrees F or 650 degrees F, indicating the maximum rise above ambient temperature on the non-fire side measured during the first 30 minutes of a standard fire endurance test. A 250 degree F temperature rise rating is considered to be the most stringent, and would meet the requirements of a specification requiring 450 degrees F or 650 degrees F.

Fire Rated Glass Testing for Windows, Doors, Walls and Floors
Both are examples of 60-90 minute temperature rise doors in an exit stairway. The door on the left has ceramic in the vision area, and therefore limited to 100 sq. inches per Table 716.5 in the 2012/2015 IBC and Table 716.1(2) in the 2018 IBC. The door on the right has fire resistive glazing in the vision area, and therefore able to exceed 100 sq. inches. The transoms and sidelites also uses fire resistive glazing rated equal to the wall.

Fire Wall Assembly Testing Standards

Fire wall assemblies are tested to ASTM E-119, Standard Test Methods for Fire Tests of Building Construction and Materials, or UL 263, Standard for Fire Tests of Building Construction and Materials. The fire rated glass product is subject to the fire endurance test, the radiant heat test and the hose stream test. If the fire rated glass product remains intact and limits the temperature rise to less than 250 degrees F above ambient on the non-fire side, the fire rated glass product passes. These products are classified as fire resistive and can be used up to the maximum size tested.

Fire Rated Glass Testing for Windows, Doors, Walls and Floors
Today’s fire restive glass systems provide even more transparency when used in clear butt-glazed wall assemblies. Refer to Tables 716.5 and 716.6 in the 2012/2015 IBC and Tables 716.1(2) and 716.1(3) in the 2018 IBC to see where ASTM E-119 rated fire resistive glazing can be used.
Fire Rated Glass Testing for Windows, Doors, Walls and Floors
Fire resistive glass and framing tested to ASTM E-119/UL 263 are now being used as part of the building envelope to exceed the size and application limitations to protected openings found in Table 705.8 in the 2012/2015/2018 IBC.

Fire Floor Assembly Testing Standards

Fire floor assemblies are also tested to ASTM E-119, Standard Test Methods for Fire Tests of Building Construction and Materials, or UL 263, Standard for Fire Tests of Building Construction and Materials. The assembly is subject to the fire endurance test and the radiant heat test. A load (typically 100 psf) is applied to the assembly for the entire duration of the test. If the assembly remains intact and limits the temperature rise to less than 250 degrees F above ambient on the non-fire side, the assembly passes. These products are also classified as fire resistive and can be used up to the maximum size tested.

Fire Rated Glass Testing for Windows, Doors, Walls and Floors
Fire resistive glass tested to ASTM E-119/UL 263 can now be used in horizontal applications such as floor and roof assemblies per Section 711 in the 2012/2015/2018 IBC.

WHEN IN DOUBT, ASK AN EXPERT

Never hesitate to consult a knowledgeable fire rated glass manufacturer if you have questions about product performance, allowed applications, or need help in understanding the code requirements. In some cases, it makes sense to involve the manufacturer in the early design phases, especially when dealing with highly technical products such as fire rated glass. With ever-changing codes and rapid advances in material technology, product and industry knowledge in the selection and use of fire rated glass products can help you save time, money and lives.

Share:
PrevNext ArticleFire Door Requirements and Sprinkler Exceptions
Previous ArticleFire Rated Glass in Unique ApplicationsNext
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • info@stage.safti.com
  • Representative Map
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
info@stage.safti.com
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

AFFILIATE COMPANIES
Division 5
1850 Grogan Ave, Merced, CA 95341
888.653.3333
Division 8
1891 Wardrobe Ave, Merced, CA 95341
866.848.2667
© 2025 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}