Skip to content
  • QUOTE
  • 888.653.333
  • info@safti.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
  • Literature
  • Specs
  • Details
  • Learn
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Gallery
  • Reps
  • Contact
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Articles
Code Education
NFPA 80 Considers Annex Note to Clear Up Framing Confusion
Code Education

NFPA 80 Considers Annex Note to Clear Up Framing Confusion

ByTJ Mababa
| April 8, 2015

NFPA 80 Considers Annex Note

The misinterpretation of IBC model building codes and NFPA 80 and 101 guidelines regarding where fire resistive-rated glazing versus fire protective-rated glazing must be used can be costly. The underlying concern pertains to the protection against the transmission of radiant heat. Fire-resistive glass and frame assemblies provide a radiant heat barrier that ensures the safe evacuation of the building, protects fire-fighters while they do their job, and reduces losses suffered by building owners. Since the codes can lead to confusion which often results in the use of insufficiently safe framing assemblies, a proposed NFPA 80 annex note that clarifies situations where fire-resistive framing must be used recently passed the first NFPA 80 Technical Committee ballot.  This article explains why NFPA 80 considers annex note to clear up framing confusion, especially in applications where fire resistive framing must be used instead of hollow metal.

Simply put, the annex note seeks to underscore that the entire assembly must fully meet the requirements of the code. When codes require fire resistive glazing, the entire framing assembly must meet the same fire resistive requirement. Combining non-fire resistive framing products, such as standard hollow metal framing, with fire-resistive glazing downgrades the entire assembly, resulting in an insufficiently safe assembly and a failure to meet the true intent of the building code. Examples abound where the authority having jurisdiction (AHJ) has ordered the removal of non-compliant assemblies.

When Hollow Metal Framing May Not Be Used

Framing systems such as hollow metal are often tested in accordance with the NFPA 252 and NFPA 257 test standards up to durations typically required for fire-resistive assembles meeting ASTM E-119. However, there are situations where such framing systems should not be used despite their demonstrated ability to meet the required duration of the fire rating. The proposed NFPA 80 annex note offers guidance about Sections 6.3.3.3 and 6.3.3.4 and explains where fire resistive framing tested to ASTM E-119 should be used to limit temperature rise and block radiant heat (see proposed annex text revision here)

NFPA 80 Considers Annex Note to Clear Up Framing Confusion
Fire resistive framing with fire resistive glazing

Here are some examples where fire-resistive assemblies are required, and framing systems such as hollow metal tested in accordance with NFPA 252 and NFPA 257 test standards are not allowed.

  • Sidelites/transom frames in 60- minute or 90-minute fire door assemblies.Where NFPA 101 and IBC 2012 require the use of 60-minute or 90-minute fire doors, hollow metal sidelite/transom frames tested only to NFPA 252 are not permitted. In a door assembly required to be rated 60 or 90 minutes, while the door and door frame may be rated 60 or 90 minutes in accordance with NFPA 252, the sidelite/transom portion of the assembly should also be tested to ASTM E-119 or UL 263. NFPA 101 and IBC 2012 require sidelites/transom portions of the assembly to be rated equal to the wall. Click here to download the NFPA 101 fire rated glazing assemblies tables. Click here for the IBC 2012 fire rated glazing assemblies tables.
  • Sidelites/transom frames in 1 and 2 hour stairwells enclosures in sprinklered buildings. While 60-90 minute temperature rise doors in 1 and 2 hour stairwells in fully sprinklered buildings may not have to meet temperature rise requirements under the IBC model building code, the sidelite/transom frames and glazing must be a fire resistive assembly (i.e., must meet ASTM E-119.) Fire-protective framing systems tested up to 90 minutes are not allowed.
  • Assemblies that exceed 25% of the wall. When sidelites/transom frames exceed 25% of a wall adjoining a partitioned space, the assemblies must meet ASTM E-119 testing requirements and must be rated equal to the wall in which they are installed. Again, framing systems such as standard hollow metal cannot be used. In this example, standard hollow metal frames, although listed up to 90 minutes or higher, cannot be used because they typically do not limit the temperature rise of the non-exposed frame surface as required by ASTM E-119.
NFPA 80 Considers Annex Note to Clear Up Framing Confusion
The glazing used in this 1-hour exit corridor exceeds 25% of the wall area. So, 60-minute fire resistive glazing and framing tested to ASTM E-119 was used in the assembly adjacent to the door.

Proposed NFPA 80 Annex Note Would Help Avoid Costly Mistakes

In November 2013, Kate Steel, a nationally recognized code consultant and NFPA 80 task group member, presented examples of improper installations of fire-rated products that were later ordered removed. These examples helped persuade the NFPA 80 Technical Committee to finalize language of a proposed annex note. “This is a positive contribution by the NFPA 80 Technical Committee to explain requirements that are often misunderstood by both design professionals and code officials,” said Steel. “I spend considerable time answering framing requirement questions unfortunately, sometimes after an improper installation has taken place. We really need to clear up confusion about framing. The proposed annex will help code users better understand the complexities of the code provisions.” Hopefully Kate’s advocacy, and that of members on the NFPA 80 Technical Committee, for the utmost fire protection whenever and wherever possible will lead to a clearer understanding on the part of specifiers, designers, and contractors regarding the safe use of fire-rated glazing systems.

Share:
PrevNext ArticleThe IBC and Exterior Fire Rated Openings
Previous ArticleMatch Fire Rated Framing and GlassNext
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • info@safti.com
  • Representative Map
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
info@safti.com

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

© 2023 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Twitter Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Videos Archive [INACTIVE]
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}