Skip to content
  • QUOTE
  • 888.653.333
  • info@safti.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
  • Literature
  • Specs
  • Details
  • Learn
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Gallery
  • Reps
  • Contact
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Articles
Code Education
Vision Panels and the Codes
Code Education

Vision Panels and the Codes

ByDiana S
| May 26, 2015

Vision Panels and Codes

Vision Panels and the Codes – Did you know that unless a vision panel is fire resistive and impact safe, it cannot be larger than 100 square inches? It is no longer true that if you have sprinklers you can make larger vision panels.

What’s an easy way to save money and create safer schools? Just add glass. The challenge is finding glass that provides the most benefits and meets the codes. Tapping into daylight through interior windows, corridor skylights, and vision panels in and around doors contributes to student safety and energy efficiency. Studies also correlate natural lighting to increased student performance.

The new 2012 IBC states that fire protection glazing, such as wired glass and ceramics, used in vision panels in 60 and 90 minute temperature rise doors located in exit enclosures and exit passageways, can be no larger than 100 square inches, whether or not the building is fully sprinklered. In addition, any vision panel needs to be within 43 inches of the floor to comply with the Americans with Disability Act (ADA.)

New 2012 IBC works to protect people from the dangers of radiant heat transmission

In the 2009 Code Development Cycle, SAFTIFIRST was able to successfully pass a code change that that removed the sprinkler tradeoff for fire rated glazing in doors located in exit enclosures and exit passageways. The new 2012 IBC Section 715.4.4.1 will read as follows with the “exception” paragraph removed (stricken):

715.4.4.1 Glazing In doors. Fire protection rated glazing in excess of 100 sq inches (0.065 square inches) is not permitted. Fire resistance rated glazing in excess of 100 sq inches (0.065msquare inches) shall be permitted in fire door assemblies when tested as components of the door assemblies, and not as glass lights, and shall have the maximum end temperature rise of 450 degrees F (250 degrees C) in accordance with 715.4.4.
Exception: The maximum transmitted temperature end rise is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.

Vision Panels and the Codes

The change is important because neither sprinklers nor fire protection glazing can fully protect against the spread of fire caused by the unrestricted radiant heat. NFPA 80 (2007) Annex 1 explains why fire resistive glazing in fire doors is important:
“Traditional glazing materials have been prohibited from being used in fire windows in exit stair enclosures because of the concern for radiant heat transfer. Recently, the model building codes also incorporated requirements for limiting the temperature rise on the unexposed face of fire doors opening into exit stair enclosures in order to address the problem of heat transfer (both conducted and reradiated) that could expose evacuating occupants passing doors at each landing. Therefore, caution should be exercised when considering glazing materials with fire protection ratings of 60 minutes or more in such applications, since they can transmit excessive radiant heat into the exit stair enclosure. However, glazing materials with fire resistance ratings are suitable for such situations, since they have been tested to limit radiant heat transfer.”

“The presence of sprinklers isn’t enough insurance when it comes to saving lives. We need balanced fire protection. Fire-rated glass plays an important role in providing both active and passive protection. Fire resistive glass products can provide the same protection as a solid wall,” said William F. O’Keeffe of SAFTIFIRST, in testimony before the International Code Council. The code council agreed with Mr. O’Keeffe and changed the code.

ADA requirements seek accessible vision areas in doors

ADA section 404.2.11 requires that at least one of the vision panels in a door and sidelites adjacent to a door be no more than 43 inches (1090 mm) above the floor line to provide visibility and safe access for all. Vision panels exceeding 100 square inches in 60 and 90 minute doors require fire resistive glazing. The resistive glass requirement applies to sidelites and transoms as well. Wired glass and ceramic products are fire protective rather than fire resistive products. This means that they fail to block the transmission of radiant heat, so their size in vision areas must be limited. In order to have vision areas in doors and sidelites in exit enclosures and exit passageways large enough to be within 43 inches of the floor line, the 2012 IBC requires this glazing to be fire resistive rather than fire protective.

The door assembly (sidelites, transoms, doors) pictured meets both the new 2012 IBC and ADA requirements for vision areas located in exit enclosures and exit passageways. These large, fire-resistive vision areas are made possible by the application of SuperLite II-XL 60 in HMTR Doors and SuperLite II-XL 60 in GPX framing in sidelites.

Vision Panels and the Codes

 

Share:
PrevNext ArticleSize Limits for Vision Panels
Previous ArticleFire Rated Code Update – 2012Next
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • info@safti.com
  • Representative Map
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
info@safti.com

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

© 2023 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Twitter Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Videos Archive [INACTIVE]
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}