Skip to content
  • QUOTE
  • 888.653.333
  • info@safti.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
  • Literature
  • Specs
  • Details
  • Learn
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Gallery
  • Reps
  • Contact
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Learn
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Reps
  • Contact
Articles
Code Education
What You Should Know About Fire-Resistant Glazing
Code Education

What You Should Know About Fire-Resistant Glazing

ByTJ Mababa
| March 20, 2019

ASTM E119/UL 263 Compliance Transforms the Range of Glazing Applications

What You Should Know About Fire-Resistant Glazing
Fire and Hurricane Rated Curtain Wall at Orlando V.A. Medical Center in Lake Nona, Fla. | Photo courtesy of SAFTI FIRST

 

What You Should Know About Fire-Resistant Glazing

The march of innovation in the built environment is relentless. Think of the advances in concrete, aluminum, steel, masonry, wood, gypsum, plastic, and MEP systems over the last 20 years and the IBC’s ever-evolving response to them. You can count on code to keep pace with the life-safety measures required to best serve the public interest.

This edition of Code Counts examines innovations in fire-rated glazing. You may know, for example, the 2018 IBC distinguishes two fire-rated categories fire-protective and fire-resistant glazing. How does the 2018 IBC define the two? How can you tell if the glazing panel you’re reviewing complies with code for the application it’s intended for? How do IBC requirements help usher in a new dimension to design freedom, structural transparency, multi-function versatility, and life-safety protection?

A Tale of Two Definitions

The 2012 IBC transformed how code officials viewed fire-rated glazing. The 2012 IBC for the first time defined the distinction between fire protection and fire resistance. The code now recognizes the fundamental differences between the two rating distinctions. According to the 2018 IBC Section 202, a fire protection rating is defined as “The period of time that an opening protective will maintain the ability to confine a fire as determined by test specified in Section 716. Ratings are stated in hours or minutes.” Fire resistance is defined in Section 202 as “That property of materials or their assemblies that prevents or retards the passage of excessive heat, hot gases or flames under conditions of use.”

Underscore those words “… excessive heat, hot gases …” in the above definition. Fire protective glazing is engineered to block the visual elements of fire, namely the flames and smoke, through the rating period, such as 20 minutes. It compartmentalizes smoke and flames.

Fire resistance takes that barrier capability to a new level. A fire resistance rating signifies the glazing not only blocks flame and smoke but also “excessive heat, hot gases” which aren’t visible but can pose an extreme threat to life-safety.

“Code officials have an outstanding understanding of the IBC. The issue today is glazing can now function as an ASTM E119/UL 263 compliant barrier wall, not just a window or storefront curtain wall,” observes Tim Nass, vice president of sales for SAFTI FIRST, a leading glazing manufacturer. “Fire-resistant glazing is transparent. So when a transparent material is specified for a 120-minute application, including blocking radiant heat, it’s understandable why it might raise questions with the code official.”

This chart illustrates the extreme differences between fire protective- and fire resistant-rated glazing as it relates to radiant heat transmission. Glazing rated as fire resistant-rated offers building occupants a passive life-safety shield that can be counted on to continuously perform even after the unlikely but possible failure of an active fire suppression system.

A new generation of fire resistant-rated glazing is compliant to the ASTM E119 or UL 263 test standards (2018 IBC 703.2). For applications that require a fire-resistance greater than one hour (2018 IBC 716.1 (2)), such as firewalls and interior exit stairways and ramps, fire-resistant glazing offers architects a code-compliant means to integrate transparent wall systems into the structural design without bargaining for a special purpose deluge sprinkler system trade-off that requires prior AHJ approval.

More Fire-Resistant Glazing Applications

For architects and building owners and developers faced with implementing an alternate assembly using special purpose deluge sprinkler systems with fixed glazing assemblies in 1-2 hour fire resistive applications, an ASTM E119/UL 263-compliant glazing solution is welcome news. The alternative sprinkler-based approach, subject to AHJ approval, can include a wide range of time-consuming and costly considerations:

  • • Preparing documented proof that the design and installation requirements are met
  • • Hydraulic calculations for each installation
  • • Ensuring an automatic, dedicated water supply capable of supplying 1 or 2 hours of water, depending on application requirements
  • • Upgrading pumps and pipes to ensure prescribed water pressure for each installation
  • • Ongoing sprinkler system maintenance

Not to mention that sprinklers can, and do, fail. As the National Fire Protection Association (NFPA) has reported, sprinklers operate effectively only 87 percent of the time. The NFPA reported the majority of sprinkler failures occurred because the system was shut off, water from the system failed to reach the fire, or not enough water was released. These failures could be caused by a number of factors, including manual tampering, lack of maintenance, low water pressure, or damage to the system a real possibility during natural disasters such as earthquakes. When the sprinkler system fails to operate, the non-rated fixed glazing assemblies, in turn, fail to compartmentalize smoke, flames and radiant heat. Safe egress is often impossible.

What You Should Know About Fire-Resistant Glazing
A fire-rated glass stairwell | Photo: SAFTI FIRST

The specification of an ASTM E119/UL 263 glazing solution presents the architect with reliable, 24/7 protection without the need for mechanical triggers. A fire-resistant glazing solution also expands the design possibilities for 2-hour fire rating applications, such as stairwells, elevator enclosures, and curtain walls.

What You Should Know About Fire-Resistant Glazing
21c Museum Hotel in Nashville, Tenn features a 1-hour fire resistive glazed floor system | Courtesy of SAFTI FIRST | Photo: Mike Schwartz

Opening up the structure to even more natural light creates an aesthetic that’s increasingly popular with building owners, developers, and tenants. Code officials should anticipate more structures incorporating fire-resistant glazing in areas once thought of as off-limits to transparent design materials. “I frequently present to code officials,” Nass says. “They always ask the right questions. They want to be certain about testing and compliance. They never want to put anyone in danger.”

How to Identify a Fire-Resistant Glazing Product

To assist code officials in determining if a glazing product meets 2018 IBC standards, code officials are encouraged to review Table 716.1(1), Marking Fire-Rated Glazing Assemblies:

More detail about 2018 IBC Table 716.1(1) is available at Section 716.1.2, especially Sections 716.1.2.2.3 – 716.1.2.3.1.

Effective with the 2012 IBC, glazing manufacturers are required to stencil onto the glazing product itself the testing standards the products has passed from a nationally recognized testing laboratory (NRTL). The stencil features the marking code noted in Table 716.1(1) and appears similar to this sample in a 2” x 1.25” format:

This sample stencil, for example, informs the code official what standards the glazing product complies with. The D, H, and T indicate that it meets NFPA 252/UL 9/UL 10 B with hose stream and the temperature rise door criteria. OH means it meets NFPA 257/UL9. W means it meets ASTM E-119/UL263. 60 means it was fire tested to 60 minutes. ULC designation means the product is also listed in Canada. Finally, the stencil shows the glazing meets ANSI Z97.1 and CPSC Cat. II, the maximum impact safety standard.

Special Fire-Resistant Glazing Applications

What You Should Know About Fire-Resistant Glazing
Fire-resistant glass with security glazing forms single assembly protection against fire, bullets, blast, and forced entry | Photo courtesy of SAFTI FIRST

Fire-resistant glazing may also be customized to broaden its application across a variety of security and environmental applications. Fire-resistant glass can also be combined with security glazing to form a single assembly that protects against fire, bullets, blast, and forced entry. For architects and building owners, the multi-function capability simplifies specification. For code officials, single-source responsibility and manufacturing help testing and listing verification.

Fire-resistant glazing can also be manufactured to meet hurricane code standards, including Florida and Texas Product Approval Numbers, and UL certifications.
Notable examples of the fire-resistant glazing in action include the $211 million Weed Army Community Hospital in Fort Irwin, Calif., the $600 million Orlando V.A. Medical Center in Lake Nona, Fla., and the $330 million San Jose Regional Medical Center in San Jose, Calif.

Learn More

To learn more about fire-rated glazing and framing components, review the 2018 IBC, especially Chapter 7 – Fire and Smoke Protection Features. Comprehensive product information including datasheets, Health Product Declarations, and the ICC-registered continuing professional education program, Designing with Fire Rated Glass (.10 ICC CEU), is available at the SAFTI FIRST website.

Share:
PrevNext ArticleInnovations in Fire Rated, Temperature Rise Glass Doors
Previous ArticleFire Rated Glass Embraces Low-Iron Glass TrendNext
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • info@safti.com
  • Representative Map
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
info@safti.com

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

© 2023 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Twitter Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Videos Archive [INACTIVE]
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}